Voxgen™ Generators
Voxgen™ mobile GeneratorSpecifications
Choose Specs
Danmik Power’s mobile generators are mounted to custom built trailers specially designed for transporting our mobile generator sets with maximum safety at highway speeds.
Our mobile generators range from 10KvA to 500kvA and are powered by EPA certified engines. These are complete ready to run generator sets with DOT rated integral tank trailers with overflow breather and baffling.
Standard equipment includes a heavy-duty Voxgen™ canopy with hinged doors, critical grade exhaust silencer, battery, oil, anti-freeze, and full output circuit breaker. The standard analog control panel provides full instrumentation with voltmeter, frequency meter, percent of load meter, oil pressure gauge, hour meter, coolant temperature gauge, fuel level gauge, and battery voltmeter.
All trailers come equipped with a fuel tank built into the trailer, mechanical or air brakes with safety disconnect and 7 wire connector, ALKO or Burquip axle(s), front jockey wheel, two rear stabilizer jacks, lighting, and license plate bracket. Spare wheel is located inside the canopy.
DANMIK 1500RPM DIESEL POWERED MOBILE GENERATORS Characteristics
Experience unmatched power and reliability with the Voxgen 1500RPM diesel-powered generators. Engineered for superior performance, our generators ensure consistent and efficient power supply, making it ideal for both residential and commercial use. Its robust 1500RPM engine guarantees longevity and minimal maintenance, while the diesel power ensures fuel efficiency and cost-effectiveness. Whether for emergency backup or continuous use, the Voxgen is your ultimate power solution.
- Versatile Power Range: Available from 10 to 1500 kVA as standalone units, meeting various power needs.
- High Efficiency: Optimal fuel consumption for longer operation.
- Durability: Engineered to withstand demanding conditions.
- Reliability: Consistent power output for critical applications.
- Scalability: Can be synchronized for higher power demands.
- Mobility: Generators can be mounted onto road ordinance trailers utilizing top-tier trailer components.
- Ease of Use: User-friendly controls and maintenance features.
Power your world with confidence. Choose Voxgen diesel-powered generators.
Generator’s Base & Canopy
Canopy: Voxgen™ has been designed with ease of maintenance as the main consideration for the end user. The Hybrid canopy fabricated entirely in-house is constructed out of 1.6mm
mild steel or 3CR12 stainless (coastal spec) and powder coated to ensure the best protection from the weather. All the panels are easily removed to allow access to any part of the unit for maintenance.
Fuel Tank: The base integrated fuel tank is constructed from 3 – 5mm mild steel or 3CR12 (coastal spec) and is fitted with an easily removable inspection cover for maintenance checking and cleaning. The tank is also equipped with VDO fuel level sender unit which can be integrated with all makes of Genset controllers for accurate fuel monitoring. A lockable drain tape is fitted to the base of the tank for fuel drainage and the entire lid of the tank is pitched to a drain hole to double as a drip tray for the engine and to facilitate ease of cleaning the engine compartment. Filling is made easy with a stainless screw lid with sieve and filter combination.
Attenuation: All units are attenuated to 75dba at a distance of 7m; this is achieved by the use of fire-retardant acoustic dampening foam blankets.
Generator’s Control Unit
Type: Standard: Deep Sea 4520 MKII
Features:
• Manual/Auto Start
• Back-lit graphical LCD display.
• Programmable front panel.
• Data Display: Frequency/battery voltage/running hours.
• Input configurable in NO/NC mode.
• Three configurable auxiliary outputs.
• Low power consumption 100mA @ 12v & 50mA @ 24v.
Protection Functions:
• Emergency Stop: Delay 0.2 seconds/action stop.
• Low battery voltage: Delay 5 seconds/action stop warning.
• Over/under speeding: Delay 2 seconds/action stop.
• High water temperature: Delay 2seconds/action shop.
• Low oil pressure: Delay 2seconds/action stop.
• Cranking time: 10 seconds.
• Crank Disconnect: 0.5 Seconds/16Hz.
• Protection hold-off timer: 10 seconds, achieved by the use of fire retardant acoustic
dampening foam blankets.
Type: Deep Sea 7310 & 7320
Features:
The DSE7310 and DSE7320 are control modules for single gen-set applications. The modules have been developed from the successful DSE5310 and DSE5320 Series and incorporate a number of advanced features to meet the most demanding on-site applications. The DSE7310 is an Automatic Start Control Module and the DSE7320 is an Auto Mains (Utility) Failure Control Module. Both modules have been designed to start and stop diesel and gas generating sets that include electronic and non-electronic engines. The DSE7320 includes the additional capability of being able to monitor a mains (utility) supply. Both modules include USB, RS232 and RS485 ports as well as dedicated DSENet® terminals for expansion device connectivity. The modules are simple to operate and feature a user-friendly menu layout for improved clarity. Enhanced features include a real time clock for enhanced event and performance monitoring, ethernet communications for low-cost monitoring, mutual standby (DSE7310 only) to reduce engine wear and tear and preventative maintenance features to detect engine part faults prior to a major problem occurring.
View build configurations
Coupling:
SAE DIRECT COUPLING BELL HOUSING & FLEX PLATE
All units rated at:
0.8 POWER FACTOR 400 VOLT 50Hz S1 CONT. DUTY 125/40 DEGREE CLASS H.
Connection type:
3 PHASE / 4 WIRE
Build configuration key:
SAT = SOUND ATTENUATED CANOPY WPC = WEATHERPROOF CANOPY
SAWPC = SOUND ATTEUNAUTED WEATHER PROOF CANOPY OS = OPEN SKID
All units are manufactured from either 3CR12 stainless steel or mild steel depending upon the environment; the canopies are designed based on a “modular” concept allowing for easy access for maintenance. After fabrication all panel work including the base is disassembled degreased and epoxy powder coated to customer colour and specification. Pyrosorb fire retardant acoustic dampening material is fastened to the inner wall of the panels to achieve the desired acoustic level. The fuel tank is integrated into the duplex base and is capable of carrying fuel for 12 operating hours for the specific size unit up to a maximum of 1000 Liters. The lid of the tank is fabricated into a “v” shape and sloped to the rear of the enclosure to act as drip tray beneath the engine and is regulated with a stop gok valve. The base of the unit is designed upon the modular concept and will not deform when lifted.
Panel configuration key:
KS = KEY START
AMF = AUTOMATIC MAINS FAILURE
All panels are manufactured in-house and tailored to suite the end user, full mains failure panels utilizing either deep sea electronics are manufactured within IP legislated housings completed with motorized or mechanically and electronically interlocked contactors. Basic key start panels with engine protection can also be made up on request.